Vacuum Circuit Breaker

General Features

It is the most secure systems arc-extinguishing technique in the vacuum condition.  ARC VACUUM TUBE extinguished the air is completely evacuated section. Vacuum tube has been manufactured with technique of welding / soldering and it is a closed system to external factors. Contact surfaces cannot be oxidized due to the oxidation is not. There are two types; side and front mechanism.



Advantages

  • Long-lived
  • Maintenance-free
  • environmentally-friendly system
  • explosion does not occur, does not harm the environment
  • very safety system.


Technical Features

Rated voltage

36kV

17.5kV

12kV

7.2kV

Lightning impulse voltage

170kV

95kV

75kV

60kV

Power frequency impulse voltage

70kV

38kV

28kV

20kV

Rated frequency

50Hz

Rated current

630A-1250A

630A-1250A-2500A

Rated short-circuit current

16kA

Rated short-circuit closing current

2.5 x Rated short-circuit current

Short-circuit time

3sec

The number of poles first opened

1.5

Temporary recovery voltage

IEC 62271

Break time

Less than 80 milisec

Closing time

Less than 120 milisec

Phase mismatch between the poles at opening and closing

Less than 5 milisec

Electrical withstand

10000-30000

Mechanical withstand

Idle 2000 on-off

 

 